Transmitter Typ: MU411
adjustment range: -220 to 850°C
application: Digital two-wire transmitter converts Pt-100, DIN EN 60751 measuring resistors
into a 4…20mA current signal.
For installation on a standard rail according to EN50022 (DIN, top hat rail).
Get offer
Downloads
Approvals
Case dimensions
B x H x T : 13 x 110 x 110 mm
Protection class
Case: IP68
Clamps: IP 00
electrical connection
See technical details page 16.0601
adjustment range
-200°C...0...+850°C
Burden
Rb [ Ohm ] = ( Ub [ V ] - U-Power supply_min [ V ] ) / 0,0215 [ A ]
Ambient temperatures
- 40 ... + 85°C
Ex protection
II 1 G Ex ia IIC T6/T5/T4 Ga
II 1 D Ex ia IIIC T135°C/T100°C/T85°C Da
II 3 G Ex nA IIC T6/T5/T4 Gc
Option
see technical data sheet